Causes and Solutions for Cable Overheating: A Guide for Inverter Users
Root Causes of Cable Overheating
Cable overheating accelerates system aging and may cause fires. Based on field data, we identify five primary causes:
-
Substandard Conductors
Impure copper (e.g., recycled copper) increases resistance. According to Joule’s law (Q = I²RT), resistance increase causes exponential heat generation. -
Overloading
Continuous current exceeding cable capacity is the leading cause. Example:2.5mm² cable (rated 26A) powering a 3HP AC (14A) + water heater (10A) = 24A is near its limit.
-
Poor Heat Dissipation
-
Densely packed cables in conduits (fill rate >40%)
-
Ambient temperatures >40°C (e.g., rooftop conduits)
-
Proximity to heat sources (<0.5m)
-
-
Faulty Connections
Loose terminals, oxidation, or corrosion at inverter/connector junctions increase contact resistance. These points can reach 100°C+ while normal operation is ≤70°C. -
Insulation Degradation
Aging cables (>10 years) develop cracks allowing moisture ingress, causing leakage currents and abnormal heating.
Self-Inspection Guide
Monthly 10-minute checks prevent 80% of failures:
-
Visual Inspection
Check for:
✓ Discoloration (yellowing/browning) at terminals
✓ Deformed insulation or burnt odor
✓ Corrosion on lugs -
Current Measurement
Use clamp meter to verify load current:Example: 4mm² cable max = 32A; if reading >38A → Overload
-
Thermal Scanning
IR thermometer readings:
⚠️ >60°C (PVC) or >90°C (XLPE) indicates danger -
Insulation Test
Megger values:-
DC strings: Positive-Negative >1MΩ
-
AC output: Phase-Ground >0.5MΩ
-
Proven Solutions
1. Correct Sizing
Formula: Min. CSA (mm²) = Max Current (A) / Derating Factor
*Factors: Copper=6-8, Aluminum=3-5*
2. Load Management
-
Stagger startup of high-power devices
-
Balance phases within 10% in three-phase systems
3. Connection Integrity
-
Apply torque specified for terminals (e.g., 2.5Nm for MC4)
-
Use antioxidant gel for aluminum conductors
-
Seal with dual-wall heat shrinks
4. Thermal Optimization
-
Maintain cable spacing ≥1× diameter
-
Derate 10% for ambient >40°C
5. Quality Cables
-
Oxygen-free copper (resistivity ≤0.0172Ω·mm²/m)
-
XLPE insulation for DC strings (90°C rating)
-
Compliance with IEC 60228 or GB/T 5023
Current Carrying Capacity Table (Copper PVC Cable, 30°C Ambient)
CSA (mm²) | Current (A) | Power (kW) | Application Examples |
---|---|---|---|
1.5 | 14A | 3.0kW | Lighting circuits |
2.5 | 26A | 5.7kW | ≤5kW inverter AC output |
4 | 32A | 7.0kW | 5-7kW inverter main lines |
6 | 47A | 10.3kW | 8-10kW inverter I/O lines |
10 | 65A | 14.3kW | Three-phase inverters |
16 | 92A | 20.2kW | Commercial systems |
💡 *Power basis: 220V×Current (1-phase), 380V×Current×1.732 (3-phase)*
Inverter Sizing Guide (Copper Cables)
Inverter Power | DC Input (PV) | AC Output | Critical Requirements |
---|---|---|---|
≤3kW | 4mm² | 2.5mm² | UV-resistant insulation |
3-5kW | 6mm² | 4mm² | Double-insulated |
5-10kW | 10mm² | 6mm² | Flame rating B1 |
≥10kW | 16mm²+ | 10mm²+ | Steel-armored construction |
Example: 7kW 3-phase inverter AC current = 7,000W/(380V×1.732×0.8)≈32A → Select 6mm² (47A)
Cables are the lifelines of PV systems. Investing in proper sizing + premium cables + scheduled maintenance boosts efficiency by 15%. When selecting inverters, request our free cable sizing tool and thermal inspection protocol to build a future-proof energy solution.